Battery Sizing Calculator
AS 1851-2012 Appendix F – Fire Alarm Panel Batteries
Standby (Quiescent) Load
24h standard • 48h critical • 72h high-security
Alarm Load
0.5h (30 min) standard per AS 1670.1
Capacity Factors
2.0 standard for ≤1 CIE connected
Installed Battery (Optional)
Enter to check pass/fail
Required Battery Capacity
Required Capacity
—
Status
—
Calculation Breakdown
Standby: I₀ × T₀
—
Alarm: Fc × IA × TA
—
Subtotal (before L)
—
Required: Subtotal × L
—
Formula: C₂₀ = L × [(I₀ × T₀) + Fc × (IA × TA)]
Save Calculation
Sign in to save this calculation to your account
Common SLA Battery Sizes
| Capacity | Typical Use | Dimensions (approx) |
|---|---|---|
| 1.2 Ah | Small panels | 97 × 43 × 52 mm |
| 2.2 Ah | Light duty | 178 × 34 × 60 mm |
| 4.0 Ah | Medium panels | 90 × 70 × 101 mm |
| 7.0 / 7.2 Ah | Standard | 151 × 65 × 94 mm |
| 12 Ah | Larger systems | 151 × 98 × 95 mm |
| 17 Ah | Heavy duty | 181 × 76 × 167 mm |
| 24 Ah | Large installations | 166 × 175 × 125 mm |
Always verify physical dimensions fit enclosure.
Standards Reference
AS 1851-2012 – Routine service of fire protection systems and equipment (Appendix F)
AS 1670.1 – Fire detection, warning, control and intercom systems
AS 1670.4 – Sound systems and intercom equipment
We provide no warranty or guarantee for the use of this tool or its accuracy. In no event will we be liable for any loss or damage, including, without limitation, indirect or consequential loss or damage, or any loss or damage arising from loss of data or profits arising out of, or in connection with, the use of this tool.