CA16 Pressure Test

CA16-1962 pressure calculation for sprinkler systems at height

📋 Report Details

No Logo

Company Name

License # | Phone

Test Inputs

Pressure measured while system is flowing full 2" / 50mm waste
kPa
Static pressure with no flow
Vertical distance from test point to highest sprinkler head
~3 levels
Based on 3.5m per level
Equivalent Height Pressure Loss
kPa
Height × 9.81 kPa/m
Pressure at Highest Head
kPa
Running − Height Loss

Compliance Checks

Sufficient Pressure (OH > 5 PSI)
Minimum pressure at highest head
5/8's Rule
Running ≥ 5/8 × Standing
CA16-1962 — This calculation determines if adequate pressure exists at the highest sprinkler head after accounting for elevation losses. The 5/8's rule ensures sufficient flow capacity remains in the supply.

💾 Want to save your tests?

Sign in to save results, add site details, and generate professional PDF reports.

Sign In / Create Free Account

Quick Reference

Minimum Pressure at Head

Ordinary Hazard: > 5 PSI (34.5 kPa)
Light Hazard: > 15 PSI (103.4 kPa)

Hydrostatic Head

9.81 kPa per metre
0.433 PSI per foot

5/8's Rule

Running pressure must be at least
62.5% of standing pressure

We provide no warranty or guarantee for the use of this tool or its accuracy. In no event will we be liable for any loss or damage, including, without limitation, indirect or consequential loss or damage, or any loss or damage arising from loss of data or profits arising out of, or in connection with, the use of this tool.