π¬ Flow Test Pro
Automatic test point calculation with pitot tube manometer readings
Test Type
AS 2941: Test at 100%, 130%, and 150% of rated pump duty
π Pitot Tube Setup
Y-Coefficient: β L/min per βinHg
β½ Pump Rating
L/min
kPa
π Test Plan
Flow to each manometer reading. Readings are rounded to whole inches (manometer readable above 2").
| Test Point | Manometer | Target Flow (L/min) | Actual Flow (L/min) | Status |
|---|
Test Points Required
β
measurements to record
βοΈ Record Achieved Results
Enter your actual test readings. The tool will compare against required minimums.
| Test Point | Achieved inHg | Achieved Flow (L/min) | Achieved Pressure (kPa) | Result |
|---|
Standards Reference
AS 2941 Pump Performance Requirements:
- 100% Duty β Rated flow at rated pressure
- 130% Duty β 130% flow at minimum 80% pressure
- 150% Duty β 150% flow at minimum 65% pressure
We provide no warranty or guarantee for the use of this tool or its accuracy. Always verify calculations against applicable standards. In no event will we be liable for any loss or damage arising from the use of this tool.