Hydrant Flow Test
Simplified hydrant flow test calculator for field use
π Report Details
No Logo
Company Name
License # | Phone
Test Data
Static = no flow (closed). Residual = measured while all outlets are flowing.
Flow Outlets
Configure each outlet used during the test. Flow is calculated from residual pressure.
Outlet 1
β L/s
β AS 2419.1:1994 Cd for 25mm nozzle
Up to 3 outlets
Total Combined Flow
β L/s
System Requirements
L/s
kPa
Enter the minimum flow and pressure required by your system.
Overall Result
β
Method: Q = Cd Γ A Γ β(2 Γ P / Ο)
Nozzle flow per AS 2419.1
Nozzle flow per AS 2419.1
Supply Curve
Supply Curve
Pass
Fail
πΎ Want to save your tests?
Sign in to save results, add site details, and generate professional reports.
Sign In / Create Free AccountQuick Reference
Australia (AS 2419.1)
| System Type | Flow | Pressure |
|---|---|---|
| Feed Hydrant | 10 L/s | 200 kPa |
| Unassisted Attack Hydrant | 10 L/s | 350 kPa |
| Assisted (Brigade Boosted / Gravity Tank) Attack | 10 L/s | 700 kPa |
| Onsite Hydrant Pump Attack | 5 L/s | 700 kPa |
Australia β NSW
| System Type | Flow | Pressure |
|---|---|---|
| Feed Hydrant | 10 L/s | 150 kPa |
| Unassisted Attack Hydrant | 10 L/s | 250 kPa |
| Assisted (Brigade Boosted / Gravity Tank) Attack | 10 L/s | 700 kPa |
| Onsite Hydrant Pump Attack | 5 L/s | 700 kPa |
UK (BS 9990)
| System Type | Flow | Pressure |
|---|---|---|
| Residential (1β2 storey) | 8 L/s | 1.7 bar |
| Residential (2+ storey) | 20β35 L/s | 1.4 bar |
| Commercial / Industrial | 25 L/s | 1.4 bar |
| Wet Riser Landing Valve | 25 L/s | 8 bar |
USA (NFPA)
| System Type | Flow | Pressure |
|---|---|---|
| Minimum Fire Hydrant | 500 gpm | 20 psi |
| Residential Area | 1,000 gpm | 20 psi |
| Commercial / Industrial | 1,500β3,000 gpm | 20 psi |
| High Value District | 3,500+ gpm | 20 psi |
Standards Reference
AS 2419.1:1994 β Fire hydrant installations - System design, installation and commissioning
BS 9990 β Non-automatic fire-fighting systems in buildings
NFPA 291 β Recommended Practice for Fire Flow Testing and Marking of Hydrants
We provide no warranty or guarantee for the use of this tool or its accuracy. In no event will we be liable for any loss or damage, including, without limitation, indirect or consequential loss or damage, or any loss or damage arising from loss of data or profits arising out of, or in connection with, the use of this tool.