Pipe Pressure Loss Calculator

Hazen-Williams friction + static head for fire system pipe sizing

Pipe & Flow Parameters

Flow Rate System demand
Pipe Schedule Wall thickness
AU standard
Nominal Size Pipe size
ID: 102.3 mm
Pipe Length Straight pipe run
90Β° Elbows Number of elbows
= 0m equivalent
Tees (branch) Flow turned 90Β°
= 0m equivalent
Rise Elevation increase
= 0 kPa static loss
Fall Elevation decrease
= 0 kPa static gain
C-Factor Hazen-Williams
roughness coefficient

Pipe Material (C-Factor)

Select a pipe material or enter a custom C-factor above

Pressure Loss Results

β€”
Friction Loss
β€”
Per Metre
β€”
Per 100m
β€”
Velocity
β€”
⚠️
HAZEN-WILLIAMS FORMULA
P = 6.05 Γ— 10⁡ Γ— Q^1.85 / (C^1.85 Γ— d^4.87) Γ— L

Save Calculation

Pipe Size Reference

Click a row to use that pipe size (uses schedule selected above)

Nominal Size Internal Ø (mm) Internal Ø (in) Typical Use

Velocity Guidelines

Condition Max Velocity Notes
AS 2118.1 Sprinklers6 m/s (20 ft/s)General limit for sprinkler systems
AS 2419.1 Hydrants10 m/s (33 ft/s)Hydrant mains and risers
Pump suction1.5 m/s (5 ft/s)To prevent cavitation
Pump discharge4.5 m/s (15 ft/s)Recommended design velocity
Underground mains3 m/s (10 ft/s)Typical design velocity

Standards Reference

AS 2118.1 β€” Automatic fire sprinkler systems

AS 2419.1 β€” Fire hydrant installations

NFPA 13 β€” Standard for the Installation of Sprinkler Systems

NFPA 24 β€” Standard for the Installation of Private Fire Service Mains

We provide no warranty or guarantee for the use of this tool or its accuracy. In no event will we be liable for any loss or damage, including, without limitation, indirect or consequential loss or damage, or any loss or damage arising from loss of data or profits arising out of, or in connection with, the use of this tool.