๐ Hydrant System Designer
Ring main hydraulic calculations for fire hydrant systems โ AS 2419.1
1 Building & Design Requirements
AS 2419.1 Table 2.1 โ typically 2 for warehouses <24,000mยฒ
Distributed evenly around ring main
2 Ring Main Configuration
AS 2419.1 minimum DN100
At property boundary, single feed to ring main
Perimeter: 300 m
Spacing: 25 m
Path to remote: 150 m
3 Booster Assembly (Town Main Fed)
H-pattern booster per AS 2419.1 Figure 7.2 โ town main โ suction hydrants โ booster inlets โ check valve โ ring main
Booster Discharge Fittings (included automatically)
โ Gate valve (isolation)
โ Check valve (NRV)
โ Elbows (as selected)
โ Tee into ring main
4 Hydrant Risers (Dual Outlet)
AS 2419.1 requires DN100 min for dual outlet hydrants
5 Isolation Valves (AS 2419.1 Fig K12)
Ring main must be isolatable into sections of not less than 20% and not more than 33% of total length. This requires 3 to 5 valves on the ring main.
Sluice valves per Figure K13
Adjacent to ring main connection
Isolation Section Check
Checking...
Also required (not calculated): Isolating valves on branches supplying more than one hydrant,
and on branches leading into buildings.
6 Hydraulic Results
Calculating...
System hydraulic analysis
Booster Outlet
โ
kPa required
Design Flow
โ
L/min
Booster Pipe
โ
kPa
Ring Friction
โ
kPa
Riser Friction
โ
kPa
Static Head
โ
kPa
โณ
Ring velocity โค 6 m/s
โณ
Hydrant spacing โค 60m
โณ
Riser โฅ DN100
โณ
Ring main โฅ DN100
โณ
Valve sections 20-33%
Pressure Breakdown
| Component | Description | Loss (kPa) |
|---|
View Detailed Calculation
Calculation details will appear here...
This tool provides preliminary calculations only. Final designs must be verified by a qualified fire protection engineer. We provide no warranty or guarantee for the use of this tool or its accuracy.