Orifice plate sizing validation per ISO 5167 / ASME MFC-3M
Enter your orifice and pipe dimensions to check if the beta ratio is within acceptable limits.
Enter your pipe size and desired beta ratio to find the optimal orifice diameter.
Enter your orifice size and desired beta ratio to find the minimum pipe diameter.
| Beta Range | Status | Notes |
|---|---|---|
| 0.10 β 0.19 | Usable | Very high ΞP, limited turndown |
| 0.20 β 0.50 | Optimal | Best Cd stability, good ΞP signal |
| 0.50 β 0.70 | Good | Standard range, reliable |
| 0.70 β 0.75 | Acceptable | Upper standard limit |
| 0.75 β 0.80 | Marginal | Some standards permit, reduced accuracy |
| > 0.80 | Not Recommended | Cd unstable, poor ΞP signal |
| Nominal Size | Sch 40 ID (mm) | Optimal Orifice (Ξ²=0.65) |
|---|---|---|
| DN50 / 2" | 52.5 | 34 mm |
| DN65 / 2Β½" | 62.7 | 41 mm |
| DN80 / 3" | 77.9 | 51 mm |
| DN100 / 4" | 102.3 | 66 mm |
| DN150 / 6" | 154.1 | 100 mm |
| DN200 / 8" | 202.7 | 132 mm |
ISO 5167-1:2022 β Measurement of fluid flow by means of pressure differential devices
ASME MFC-3M β Measurement of fluid flow in pipes using orifice, nozzle, and venturi
AS 2419.1 β Fire hydrant installations (Australian)
We provide no warranty or guarantee for the use of this tool or its accuracy. In no event will we be liable for any loss or damage, including, without limitation, indirect or consequential loss or damage, or any loss or damage arising from loss of data or profits arising out of, or in connection with, the use of this tool.